Block that outputs the supply air temperature setpoint, as well as the control signals for the cooling and heating coils in a fan coil unit system. The implemented sequence is based on ASHRAE Guideline 36, 2021, Part 5.22.4.
The supply air temperature TSupSet is varied from
the zone cooling setpoint temperature TZonCooSet to
the minimum supply air temperature for cooling
TSupSet_min, when the cooling loop signal
uCoo varies from the minimum limit
uCoo_min to the maximum limit uCoo_max.
Similarly, TSupSet is varied from the zone heating
setpoint temperature TZonHeaSet to the maximum supply
air temperature for heating TSupSet_max, when the
heating loop signal uHea varies from the minimum limit
uHea_min to the maximum limit uHea_max.
The setpoint in deadband mode is equal to the current measured
supply air temperature TAirSup. yCooCoi
and yHeaCoi are set to zero when the fan proven on
signal u1Fan is false.