.Buildings.DHC.ETS.Combined.Controls.PredictLeavingTemperature

Block that predicts heat exchanger leaving water temperature

Information

This block computes the predicted heat exchanger leaving water temperature as used in Buildings.DHC.ETS.Combined.Controls.WatersideEconomizer.

The predicted heat exchanger approach is computed as

dTApp = dTApp_nominal * m2_flow / m2_flow_nominal,

which gives the predicted heat exchanger leaving water temperature as

T2WatLvg = T1WatEnt + dTApp.

Revisions


Generated at 2026-06-25T20:19:00Z by OpenModelicaOpenModelica 1.26.9 using GenerateDoc.mos