This model validates Buildings.Fluid.Chillers.ModularReversible.TableData2DLoadDep against the polynomial chiller model Buildings.Fluid.Chillers.ElectricReformulatedEIR for water-cooled chiller applications.
ref reads the reference results obtained
from that model.There is good agreement with the reference results, except
during the model time interval [7200, 7900] s, where
the polynomial model computes zero capacity and power. This
discrepancy stems from the existence of multiple solutions in the
polynomial model. The reference results show one solution with
TEvaLvg = TEvaEnt = 20 °C. This temperature exceeds the
upper limit per.TEvaLvgMax of the polynomial model's
validity range, resulting in a negative capacity that is bounded to
0 in the polynomial model. The data table model reveals that
an alternative solution exists where the CHW setpoint is met with a
PLR value of about 74 %.