This model validates Buildings.Fluid.Chillers.ModularReversible.TableData2DLoadDep against the polynomial chiller model Buildings.Fluid.Chillers.ElectricEIR for air-cooled chiller applications.
ref reads the reference results obtained
from that model.There is good agreement with the reference results, except
during the time interval where the PLR value exceeds 1. In
this interval the polynomial model computes a significantly higher
cooling heat flow rate (in negative value) and a slightly higher
power. This discrepancy occurs because the polynomial model
calculates the heat flow rate at PLR ≤ 1 while calculating
power at PLR ≤ per.PLRMax. Consequently, when PLR increases
between 1 and per.PLRMax, input power increases
according to the polynomial EIRFunPLR, but the heat
flow rate only varies due to the effect of the increasing leaving
temperature as the setpoint is no longer met. This appears as a
deficiency in the polynomial model that is resolved in the data
table model.