.Buildings.Fluid.Chillers.ModularReversible.Validation.TableData2DLoadDep_HeatRecovery

Test model for chiller electric reformulated EIR

Information

This model validates Buildings.Fluid.Chillers.ModularReversible.TableData2DLoadDep against the polynomial chiller model Buildings.Fluid.Chillers.ElectricEIR for heat recovery chiller applications.

Results analysis

There is good agreement with the reference results, except during the model time interval [7500, 8100] s, where the polynomial model computes lower power. During this period, the polynomial model calculates lower power due to the evaporator leaving temperature exceeding the maximum threshold upper limit per.TEvaLvgMax. While the data table model does not extrapolate beyond the temperature values provided in the performance data file, the reference model continues using polynomial evaluation of capacity and power outside of the validity range. Consequently, the polynomial model computes a higher capacity, resulting in a lower PLR and reduced power during this interval.