Test model for the heat exchanger with input effectiveness
Validation test for the block
Buildings.Fluid.HeatExchangers.ThermalWheels.Latent.BaseClasses.HeatExchangerWithInputEffectiveness.
The input signals are configured as follows:
- The supply air temperature TSup changes from 273.15 +
30 K to 273.15 + 40 K during the period from 120 seconds
to 180 seconds.
- The sensible heat exchanger effectiveness epsSen changes
from 0.7 to 0.8 during the period from 120 seconds to
180 seconds.
- The latent heat exchanger effectiveness epsLat changes
from 0.4 to 0.8 during the period from 180 seconds to
240 seconds.
The expected outputs are:
- During the period from 60 seconds to 120 seconds, the
difference between the entering exhaust air humidity and the
leaving exhaust air humidity increases. This difference then
decreases during the period from 180 seconds to 240 seconds.
- During the period from 120 seconds to 180 seconds, the
difference between the entering exhaust air temperature and the
leaving exhaust air temperature increases.
Contents
- September 29, 2023, by Sen Huang:
First implementation.