This is the base class for heat pump models where the capacity
and input power are computed by interpolating manufacturer data
along the condenser entering or leaving temperature, the evaporator
entering or leaving temperature and the part load ratio. Toggling
the Boolean parameter is_rev enables representing
either a non-reversible (heating-only) heat pump or a reversible
heat pump.
This model is a wrapper for Buildings.Fluid.HeatPumps.ModularReversible.TableData2DLoadDep, which the user may refer to for the modeling assumptions.
The following input and output points are available.
y1, DO signal,
with a dimensionality of zerois_rev=true), heat
pump operating mode command signal: y1Hea, DO signal,
with a dimensionality of zeroy1Hea=true for heating mode,
y1Hea=false for cooling mode.THeaWatSet, AO signal, with a dimensionality of
zerois_rev=true), Heat
pump CHW supply temperature setpoint: TChiWatSet, AO
signal, with a dimensionality of zeroy1_actual, DI signal, with a
dimensionality of zero