This model validates the pump head computation algorithm implemented in Buildings.DHC.Loads.BaseClasses.FlowDistribution by comparing that model with an explicit modeling of the distribution network, the distribution pump and the terminal units.
Two configurations are tested, both with variable-flow distribution.
*CstSpe): the pump
rides its curve as the terminal units modulate the flow rate.*CstDp): the pump speed is
modulated by a PI loop tracking a Δp setpoint at a remote location
in the circuit, upstream of the last terminal unit.| Name | Description |
|---|---|
|
|
Source side medium |
|
|
Load side medium |
per. This is for #3099.