Space cooling system
This block is identical to Buildings.Examples.Tutorial.SpaceCooling.System3,
except that an air filter is added to the cooling system.
The major input signals for the air filter are configured as
follows:
- The input trace substance C_inflow.y changes from 10
µg/m³ (7.73e-9 kg/kg, assuming an air density of 1.293 kg/m³) to 15
µg/m³ (1.16e-8 kg/kg) at 12:00 (15552000+12*3600 seconds).
- The filter replacement signal
repSig is
false.
The expected output are:
- The filtration efficiency airFil.eps[1] decreases along
with the contaminant airFil.masAcc.mCon build up.
- The fan power fan.P slightly increases, caused by the
rising pressure drop across the filter as contaminants build
up.
Note that these changes in filtration efficiency and pressure
drop are relatively minor over the span of a single day, with more
pronounced effects expected over months.