.Buildings.Fluid.Chillers.ModularReversible.Validation.TableData2DLoadDep

Test model for chiller electric reformulated EIR

Information

This model validates Buildings.Fluid.Chillers.ModularReversible.TableData2DLoadDep against the polynomial chiller model Buildings.Fluid.Chillers.ElectricReformulatedEIR for water-cooled chiller applications.

Results analysis

There is good agreement with the reference results, except during the model time interval [7200, 7900] s, where the polynomial model computes zero capacity and power. This discrepancy stems from the existence of multiple solutions in the polynomial model. The reference results show one solution with TEvaLvg = TEvaEnt = 20 °C. This temperature exceeds the upper limit per.TEvaLvgMax of the polynomial model's validity range, resulting in a negative capacity that is bounded to 0 in the polynomial model. The data table model reveals that an alternative solution exists where the CHW setpoint is met with a PLR value of about 74 %.

Revisions