This model validates Buildings.Fluid.Chillers.ModularReversible.TableData2DLoadDep against the polynomial chiller model Buildings.Fluid.Chillers.ElectricEIR for heat recovery chiller applications.
ref reads the reference results obtained
from that model.There is good agreement with the reference results, except
during the model time interval [7500, 8100] s, where
the polynomial model computes lower power. During this period, the
polynomial model calculates lower power due to the evaporator
leaving temperature exceeding the maximum threshold upper limit
per.TEvaLvgMax. While the data table model does not
extrapolate beyond the temperature values provided in the
performance data file, the reference model continues using
polynomial evaluation of capacity and power outside of the validity
range. Consequently, the polynomial model computes a higher
capacity, resulting in a lower PLR and reduced power during this
interval.