Performance data record for a wet cooling cooler using the York calculation methods.
The default settings are for a cooler with a design approach temperature (cooling out - air wet bulb in) of 3.89 K and a design range temperature (cooling in - cooling out) of 5.56 K. This corresponds to a nominal water inlet temperature of 35 °C and a nominal water outlet temperature of 29.44 °C.