.Buildings.Fluid.HeatExchangers.CoolingTowers.DryCooler

Cooling tower model based on epsilon-NTU relation

Information

Model for a steady-state or dynamic dry cooling tower with a variable speed fan using epsilon-NTU method for heat transfer.

Thermal performance

To compute the thermal performance, this model takes as parameters the nominal cooling capacity, air dry-bulb temperature, and cooling fluid (water or glycol) inlet and outlet temperatures as specified in the data record Buildings.Fluid.HeatExchangers.CoolingTowers.Data.DryCooler.Generic. The cooling tower performance is modeled using the effectiveness-NTU relationship for a crossflow configuration.

Changes in convective heat transfer coefficient on the coolant-side and the air-side due to change in flow rate and temperature are taken into account using the model Buildings.Fluid.HeatExchangers.BaseClasses.HADryCoil. This correction can be configured in the data record Buildings.Fluid.HeatExchangers.CoolingTowers.Data.DryCooler.Generic.

Revisions


Generated at 2026-05-09T18:18:56Z by OpenModelicaOpenModelica 1.26.7 using GenerateDoc.mos