.Buildings.Fluid.HeatExchangers.ThermalWheels.Data.ASHRAE

ASHRAE data record for variable-speed thermal wheels

Information

ASHRAE performance dataset for the variable-speed wheel model.

It is developed based on Figure 7 in ASHRAE (2024). However, the original data set was extrapolated to cover lower values of speed ratio, i.e. <= 0.2, by setting the heat exchange effectiveness corrections to 0 when the speed ratio is 0.

References

ASHRAE (2024). Chapter 26, Air-to-Air Energy Recovery Equipment, ASHRAE Handbook—HVAC Systems and Equipment.

Definition

record ASHRAE = Buildings.Fluid.HeatExchangers.ThermalWheels.Data.Generic(final have_varSpe = true, senEff(uSpe = {0, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1}, epsCor = {0, 0.40, 0.71, 0.83, 0.90, 0.93, 0.96, 0.97, 0.98, 0.99, 1}), latEff(uSpe = {0, 0.15, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1}, epsCor = {0, 0.26, 0.37, 0.58, 0.72, 0.81, 0.86, 0.90, 0.96, 1}));

Revisions


Generated at 2026-05-09T18:18:56Z by OpenModelicaOpenModelica 1.26.7 using GenerateDoc.mos