Test model for the enthalpy recovery wheel with bypass dampers
Example for the model
Buildings.Fluid.HeatExchangers.ThermalWheels.Latent.BypassDampers.
The input signals are configured as follows:
- The operating signal uRot changes from
false to true at 72 seconds.
- The supply air temperature TSup changes from 273.15 +
30 K to 273.15 + 40 K during the period from 60 seconds
to 120 seconds. The exhaust air temperature remains constant.
- The bypass damper position uBypDamPos changes from
0 to 0.2 during the period from 200 seconds to 360
seconds.
- The supply air flow rate and the exhaust air flow rate are
constant.
The expected outputs are:
- The sensible heat exchanger effectiveness
epsSen
and the latent effectiveness epsLat are 0 at the
beginning. They become positive at 72 seconds and keep constant
until 200 seconds. After the 200 seconds, both epsSen
and epsLat decrease.
- Before 72 seconds, the temperature of the leaving supply air is
equal to TSup. Likewise, the temperature of the leaving
exhaust air is equal to that of the entering exhaust air
temperature. The temperatures of the leaving supply air and the
leaving exhaust air follow the change of TSup during the
period from 72 seconds to 200 seconds. After 200 seconds, the
leaving supply air temperature increases and the leaving exhaust
air temperature decreases.
Contents
- September 29, 2023, by Sen Huang:
First implementation.