.Buildings.Fluid.HeatPumps.ModularReversible.RefrigerantCycle.BaseClasses.Validation.TableData2DLoadDep

Information

This model validates the load calculation logic of the block Buildings.Fluid.HeatPumps.ModularReversible.RefrigerantCycle.BaseClasses.TableData2DLoadDep for different system configurations and operating modes.

The validation is carried out by computing the tracked temperature using the heat flow rate calculated by the block, and feeding back this variable along with the required part load ratio as inputs. It is then expected that the tracked temperature matches the setpoint. Further validation of the performance calculation algorithm by comparison to polynomial chiller models is available in the package Buildings.Fluid.Chillers.ModularReversible.Validation.

Revisions