This model validates the load calculation and staging logic of
the block
Buildings.Fluid.HeatPumps.ModularReversible.RefrigerantCycle.BaseClasses.TableData2DLoadDepSHC.
The two available control options are tested: the component
hpSup uses supply temperature control, while the
component hpRet uses return temperature control.
The model represents a three-module system operating in constant
simultaneous heating and cooling mode with the on/off command
always true.
The validation is carried out by computing the tracked temperature using the heat flow rate calculated by the block, and feeding back this variable as input to the heat pump model. It is then expected that the tracked temperature matches the setpoint, under the constraints of step-by-step staging and minimum stage runtime. Note that a filtered value of the tracked temperature is used to avoid creating an algebraic loop.