.Buildings.Fluid.HeatPumps.ModularReversible.Validation.TableData2DLoadDepSHC

Information

This model validates the hydronics and built-in control logic of Buildings.Fluid.HeatPumps.ModularReversible.TableData2DLoadDepSHC.

The model represents a three-module system where the HW and CHW isolation valves are modeled using an equivalent actuator. The actuator model represents the parallel network of the modules' condenser or evaporator barrels in series with the HW or CHW isolation valves. It is parameterized with the flow characteristics calculated by the heat pump model, and controlled by the output variables provided by this model. The heat pump operating mode switches between simultaneous heating and cooling, heating only, and cooling only. The on/off command starts as true and is switched to false at the end.

While the heat pump component is subjected to the design HW and CHW differential pressures and return temperatures, the supply temperature setpoints vary, creating a varying load. The validation then consists in verifying that the modules are effectively staged in various modes to adapt to the load. Additionally, it confirms that the isolation valve parameterization and controls result in HW and CHW flow rates that vary linearly with the number of enabled modules on each side.

Contents

Name Description
 Medium HW or CHW medium

Revisions