Block for fan coil unit control. It outputs supply fan enable signal and speed signal, the supply air temperature setpoint, the zone air heating and cooling setpoints, and commanded valve positions for heating and cooling coils.
It is implemented according to the ASHRAE Guideline 36-2021, Part 5.22.
The sequences consist of the following subsequences.
The supply fan control is implemented according to Part 5.22.4.
It outputs the control signals for supply fan enable
yFan and the fan speed yFanSpe. See
Buildings.Controls.OBC.ASHRAE.G36.FanCoilUnits.Subsequences.FanSpeed
for a detailed description.
The supply air temperature setpoint control sequences are
implemented based on Part 5.22.4. The block outputs a supply air
temperature setpoint signal TSupSet, and control
signals for the heating coil yHeaCoi and the cooling
coil yCooCoi. See
Buildings.Controls.OBC.ASHRAE.G36.FanCoilUnits.Subsequences.SupplyAirTemperature
for a detailed description.
The zone air heating setpoint TZonHeaSetand cooling
setpoint TZonHeaSet as well as system operation mode
signal modSetPoi.yOpeMod are described at
Buildings.Controls.OBC.ASHRAE.G36.AHUs.SingleZone.VAV.SetPoints.ModeAndSetPoints.
The plant requests are implemented based on Part 5.22.8. The
block outputs a chilled water plant request
yChiPlaReq, chilled water supply temperature reset
request yChiWatResReq, hot water plant request
yHotWatPlaReq and hot water supply temperature reset
request yHotWatResReq. See
Buildings.Controls.OBC.ASHRAE.G36.FanCoilUnits.Subsequences.PlantRequests
for a detailed description.