This model validates the load calculation logic of the block Buildings.Fluid.HeatPumps.ModularReversible.RefrigerantCycle.BaseClasses.TableData2DLoadDep for different system configurations and operating modes.
chiSupLvg validates the block for
chiller applications with CHW supply temperature control and
performance data interpolation based on evaporator and condenser
leaving temperature.chiRetEnt validates the block for
chiller applications with CHW return temperature control and
performance data interpolation based on evaporator leaving and
condenser entering temperature.chiHeaSupLvg validates the block for
heat recovery chiller applications with HW supply temperature
control and performance data interpolation based on evaporator and
condenser leaving temperature.hpSupLvg validates the block for
heat pump applications with HW supply temperature control and
performance data interpolation based on evaporator and condenser
leaving temperature.The validation is carried out by computing the tracked temperature using the heat flow rate calculated by the block, and feeding back this variable along with the required part load ratio as inputs. It is then expected that the tracked temperature matches the setpoint. Further validation of the performance calculation algorithm by comparison to polynomial chiller models is available in the package Buildings.Fluid.Chillers.ModularReversible.Validation.