This is a model for an air-to-water heat pump where the capacity
and input power are computed by interpolating manufacturer data
along the condenser entering or leaving temperature, the evaporator
entering or leaving temperature and the part load ratio. The model
can be configured to represent either a non-reversible
(heating-only) heat pump (is_rev=false) or a
reversible heat pump (is_rev=true).
This model is a wrapper for Buildings.Fluid.HeatPumps.ModularReversible.TableData2DLoadDep, which the user may refer to for the modeling assumptions. Note that, by default, internal safeties in this model are disabled.
Refer to the documentation of the base class Buildings.Templates.Components.BaseClasses.PartialHeatPumpTableData2DLoadDep for a description of the available control input and output variables.